Model |
SRT2-1000A |
SRT2-1500A |
SRT2-2000A |
SRT2-3000A |
|
Capacity |
1000VA/900W |
1500VA/1350W |
2000VA/1800W |
3000VA/2700W |
|
INPUT |
Voltage |
220V/230V/240V (Adjustable from 149.5V to 310V) |
|||
Frequency |
50Hz/60Hz ±10% auto sensing |
||||
OUTPUT |
Voltage(Battery mode) |
Pure sine wave at +/-5% nominally, -10% after low battery warming |
|||
AVR |
Output voltage will boost when input voltage is between -9% to -27.5% of nominal; output voltage will buck when input voltage is between +9% to +25% of nominal. |
||||
Frequency |
50Hz / 60Hz ±0.5% |
||||
Waveform |
Pure sine wave |
||||
Transfer time |
2 to 4 milliseconds including detection time (typical) |
||||
PROTECTION |
Overload |
UPS will automatically power off if overload exceeds 110% ofnominal at 20 seconds; 125% at 5 seconds. |
|||
Surge |
300Joules, 2ms |
||||
Short circuit |
UPS output will be cut off immediately or be protected byinput circuit breaker. |
||||
Tele-communication |
RJ45 |
||||
EMI / RFI filter |
100kHz to 10MHz |
||||
Fuse |
Yes |
||||
Alarm |
Buzzer beeps under backup mode, battery low, battery charging fault, and overload. |
||||
BATTERY |
Type |
Sealed, maintenance-free lead acid battery |
|||
Typical recharge time |
3 hours to 90% |
||||
Battery quantity |
9Ah*2 |
7Ah*4 |
9Ah*4 |
9Ah*6 |
|
GENERAL |
Protection |
Automatic diagnostics, over-discharge and short circuit protection by fuse |
|||
Dimension (W*D*H) |
428*453*84 mm |
428*563*84 mm |
428*669*84 mm |
||
Display |
LED indicator |
||||
Communication interface |
Standard – RS-232 and USB B-type; *Optional – SNMP |
||||
Audible noise |
|||||
Ambient operation |
0 to 40℃, 0 to 95% humidity (non-condensing) |