MODEL |
VRT-1000 |
VRT-1500 |
|
|
CAPACITY |
1000VA |
1500VA |
|
|
900W |
1350W |
||
|
INPUT |
Voltage |
100V / 110V / 115V / 120V / 127V / 200V / 208V / 220V / 230V / 240V |
|
|
Frequency |
50Hz / 60Hz ±2.5Hz auto sensing (45Hz to 65Hz user selectable) |
||
|
Phase |
Single phase |
||
|
Power factor |
> 0.97 |
||
|
OUTPUT |
Voltage |
220V / 230V / 240V ±2% (selectable output voltage) |
|
|
Frequency |
50Hz / 60Hz ±0.25Hz |
||
|
Waveform |
Pure sine wave |
||
|
Phase |
Single phase |
||
|
Harmonic distortion |
< 5% of T.H.D. at non-linear load |
||
|
Efficiency |
Approximately 89% |
||
|
Connections |
*Please refer below “Receptacle Options”. Customized receptacle can be discussed. |
||
|
PROTECTION |
Overload protection |
UPS automatic power off if overload exceeds 106% to 120% of nominal at 30 seconds; 121% to 150% for 10 seconds |
|
|
Short circuit protection |
UPS output cut off immediately or protected by input fuse or circuit breaker |
||
|
Tele-communication |
RJ45 |
||
|
Alarm |
Buzzer beeps under backup mode, battery low, battery charging fault, and overload |
||
|
BATTERY |
Type |
Sealed, maintenance-free lead acid battery |
|
|
Typical recharge time |
4 hours to 90% |
||
|
Battery quantity |
12V 7Ah x3 |
12V 7Ah x4 |
|
|
Backup time (100% load) |
3 to 5 minutes |
3 to 5 minutes |
|
|
Protection |
Battery low cut-off without draining any current |
||
|
GENERAL |
Dimension (W x D x H) |
428mm x 425mm x 84mm |
428mm x 500mm x 84mm |
|
Product weight |
15.2kg(33.5lb) |
20.8kg(45.8lb) |
|
|
Display (LED/LCD) |
LED – line mode (green), bypass / battery mode (yellow), fault (red) |
||
|
Communication interface |
Standard – RS-232; *Optional – USB B-type and/or SNMP |
||
|
Audible noise |
< 45dBA (1m from surface) |
||
|
Ambient temperature |
+0 °C to +40 °C |
||
|
Storage temperature |
-15 °C to +50 °C |
||
|
Humidity |
0-95%, non-condensing |
||




There are no reviews yet.