MODEL |
VGS-2000 |
VGS-3000 |
|
CAPACITY |
2000VA |
3000VA |
|
1800W |
2700W |
||
INPUT |
Voltage |
100V / 110V / 115V / 120V / 127V / 220V / 230V / 240V 1 0V-level mode: 60V to 69V under 25% load, 70V to 79V under 50% load, 80V to 89V under 75% load, 90V to 144V with 100% load |
|
Frequency |
50Hz / 60Hz ±2.5Hz auto sensing (45Hz to 65Hz user selectable) |
||
Phase |
Single phase |
||
Power factor |
> 0.97 |
||
OUTPUT |
Voltage |
100V / 110V / 115V / 120V / 220V / 230V / 240V ±2% (selectable output voltage) |
|
Frequency |
50Hz / 60Hz ±0.2Hz |
||
Waveform |
Pure sine wave |
||
Phase |
Single phase |
||
Harmonic distortion |
< 5% of T.H.D. at non-linear load |
||
Efficiency |
Approximately 89% |
||
Connections |
*Please refer below “Receptacle Options”. Customized receptacle can be discussed. |
||
PROTECTION |
Overload protection |
UPS automatic power off if overload exceeds 106% to 120% of nominal at 30 seconds; 121% to 150% for 10 seconds |
|
Short circuit protection |
UPS output cut off immediately or protected by input fuse or circuit breaker |
||
Tele-communication |
RJ45 |
||
Alarm |
Buzzer beeps under backup mode, battery low, battery charging fault, and overload |
||
BATTERY |
Type |
Sealed, maintenance-free lead acid battery |
|
Typical recharge time |
4 hours to 90% |
||
Battery quantity |
12V 7Ah x6 |
12V 7Ah x8 |
|
Backup time (100% load) |
3 to 5 minutes |
3 to 4 minutes |
|
Protection |
Battery low cut-off without draining any current |
||
GENERAL |
Dimension (W x D x H) |
225mm x 420mm x 358mm |
|
Product weight |
26.5kg(58.3lb) |
31.5kg(69.3lb) |
|
Display (LED/LCD) |
LED – line mode (green), bypass / battery mode (yellow), fault (red) |
||
Communication interface |
Standard – RS-232; *Optional – USB B-type and/or SNMP |
||
Audible noise |
< 50dBA (1m from surface) |
||
Ambient temperature |
+0 °C to +40 °C |
||
Storage temperature |
-15 °C to +50 °C |
||
Humidity |
0-95%, non-condensing |
Chưa có đánh giá nào.